کليد هوایی 1000 آمپر
کليد هوایی 1000 آمپر چهار پل کشویی سری NT قدرت قطع 42KA
Circuit breaker Masterpact NT10H1 – 1000 A – 4 poles – fixed – w/o trip unit
range of product | Masterpact NT | |
---|---|---|
product or component type | Basic frame | |
device short name | Masterpact NT10 | |
circuit breaker name | Masterpact NT10H1 | |
poles description | 4P | |
neutral position | Left | |
network type | AC | |
breaking capacity code | H1 | |
suitability for isolation | Yes conforming to IEC 60947-2 | |
utilisation category | Category B |
network frequency | 50/60 Hz | |
---|---|---|
control type | Push-button | |
mounting mode | Fixed | |
[In] rated current | 1000 A at 40 °C | |
[Ui] rated insulation voltage | 1000 V AC 50/60 Hz conforming to IEC 60947-2 | |
[Uimp] rated impulse withstand voltage | 12 kV conforming to IEC 60947-2 | |
[Icm] rated short-circuit making capacity | 88 kA 220/415 V AC at 50/60 Hz 88 kA 440 V AC at 50/60 Hz 88 kA 525 V AC at 50/60 Hz 88 kA 690 V AC at 50/60 Hz | |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 | |
circuit breaker CT rating | 1000 A | |
breaking capacity | 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2 | |
[Ics] rated service breaking capacity | 42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA at 220/415 V AC 50/60 Hz conforming to IEC 60947-2 42 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2 | |
protection type | Without protection | |
mechanical durability | 12500 cycles without maintenance conforming to IEC 60947-2 | |
electrical durability | 3000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 AC-23A: 3000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 AC-3: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 | |
connection pitch | 70 mm | |
[Icw] rated short-time withstand current | 24 kA 3 s conforming to IEC 60947-2 42 kA 0.5 s conforming to IEC 60947-2 42 kA 1 s conforming to IEC 60947-2 | |
maximum breaking time | 25 ms | |
maximum closing response time | 50 ms | |
height | 301 mm | |
width | 346 mm | |
depth | 196 mm |
standards | IEC 60947-2 | |
---|---|---|
product certifications | ASEFA LCIE | |
pollution degree | 3 conforming to IEC 60664-1 | |
ambient air temperature for operation | -25…70 °C | |
ambient air temperature for storage | -40…85 °C |