کنتاکتور اشنایدر الکتریک 400 آمپر 110 ولت AC
کنتاکتور اشنایدر الکتریک 400 آمپر
TeSys F contactor – 3P (3 NO) – AC-3 – <= 440 V 400 A – coil 110 V AC
range | TeSys | |
---|---|---|
product name | TeSys F | |
product or component type | Contactor | |
device short name | LC1F | |
contactor application | Resistive load Motor control | |
utilisation category | AC-1 AC-4 AC-3 | |
poles description | 3P | |
power pole contact composition | 3 NO | |
[Ue] rated operational voltage | <= 1000 V AC 50/60 Hz <= 460 V DC | |
[Ie] rated operational current | 500 A (at <40 °C) at <= 440 V AC AC-1 400 A (at <55 °C) at <= 440 V AC AC-3 | |
motor power kW | 75 kW at 400 V AC 50/60 Hz (AC-4) 200 kW at 380…400 V AC 50/60 Hz (AC-3) 220 kW at 415 V AC 50/60 Hz (AC-3) 250 kW at 440 V AC 50/60 Hz (AC-3) 257 kW at 500 V AC 50/60 Hz (AC-3) 280 kW at 660…690 V AC 50/60 Hz (AC-3) 185 kW at 1000 V AC 50/60 Hz (AC-3) 110 kW at 220…230 V AC 50/60 Hz (AC-3) | |
[Uc] control circuit voltage | 110 V AC 40…400 Hz |
[Uimp] rated impulse withstand voltage | 8 kV | |
---|---|---|
overvoltage category | III | |
[Ith] conventional free air thermal current | 500 A (at 40 °C) | |
rated breaking capacity | 3200 A conforming to IEC 60947-4-1 | |
[Icw] rated short-time withstand current | 3600 A 40 °C – 10 s 2400 A 40 °C – 30 s 1700 A 40 °C – 1 min 1200 A 40 °C – 3 min 1000 A 40 °C – 10 min | |
associated fuse rating | 400 A aM at <= 440 V 500 A gG at <= 440 V | |
average impedance | 0.26 mOhm – Ith 500 A 50 Hz | |
[Ui] rated insulation voltage | 1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C | |
power dissipation per pole | 65 W AC-1 42 W AC-3 | |
mounting support | Plate | |
standards | IEC 60947-1 JIS C8201-4-1 IEC 60947-4-1 EN 60947-4-1 EN 60947-1 | |
product certifications | BV UL CB ABS RINA CSA RMRoS DNV LROS (Lloyds register of shipping) |